FTT - field measuring transmitter
FTT - field measuring transmitter
Field measuring transmitter (FTT) is designed for continuous CTx and TCx initial temperature sensor signal processing to unified output DC signal according to GOST 26.011 - 4-20 mA and/or digital signal via HART, PROFIBUS-PA, FOUNDATION Fieldbus. It is a field case equipped with cable glands with installed measuring transmitter manufactured by PR Electronics (more details see at page 12-2). At the time of order it is necessary to specify required TT adjustment range.
Ambient air |
general purpose |
0ExiaIICT6 X or 1ExdIICT6 |
|||
-55 ÷ +85°С |
-55 ÷ +85°С |
Т4 |
-55 ÷ +60°С |
Т5…Т6 |
|
Version group according to GOST R 52931 |
group V3 |
||||
Dust and water protection degree |
IP 66 |
FTT |
Exi |
- |
А |
18 |
А |
- |
х |
- |
PR 5335 |
(K, 0…600°С) |
1 |
2 |
|
3 |
4 |
5 |
|
6 |
|
7 |
8 |
NN |
Parameter name |
Code |
Description |
|||
1 |
Type |
FTT |
field measuring transmitter |
|||
2 |
Explosion protection |
Not filled |
general purpose |
|||
Exi |
0ExiaIICT6 X, intrinsically safe circuit |
|||||
Exd |
1ExdIICT6, explosion-proof enclosure |
|||||
3 |
1st cable gland |
А |
for unarmoured cable in metal hose RZCH-15 |
|||
В |
for unarmoured cable in metal hose MRPI-15 |
|||||
C |
for unarmoured cable in metal hose DN18 |
|||||
D |
for unarmoured cable in metal hose DN20 |
|||||
E |
for unarmoured cable in metal hose DN12 |
|||||
F |
for pipe assembly, output external thread M20x1,5 |
|||||
G |
for pipe assembly, output external thread G1/2 |
|||||
H |
for unarmoured cable, 6.5 - 14 mm diameter |
|||||
I |
for unarmoured cable, 3.2 - 8.7 mm diameter |
|||||
J |
for cable with internal/external sheath diameter: 6,1-11,7/9,5-15,9, single-line wire armoured cable |
|||||
К |
for cable with internal/external sheath diameter: 3,1-8.7/6,1-11,5, all armour types |
|||||
L |
for cable with internal/external sheath diameter: 6,5-14/12,5-20,9, all armour types |
|||||
4 |
Case modification |
18; 19 |
aluminium head |
IP66 |
1ExdIICT6 / 0ExiaIICT6 X / general purpose |
|
14 |
aluminium head |
IP66 |
0ExiaIICT6Х or general purpose |
|||
44.45 |
aluminium box |
IP66 |
0ExiaIICT6Х or general purpose |
|||
5 |
2nd, 3rd, 4th |
A, B, C …. |
see "code" field for the 1st cable gland |
|||
6 |
Number of measuring transmitters |
1 |
for cases 14, 18 ,19, 44 |
case description see in tables №1b and №2 |
||
2 |
for case 44, 45 |
|||||
4 |
for case 45 |
|||||
7 |
Measuring transmitter modification |
PR 5331 |
4-20mА |
Supports thermocouples and resistance thermometers |
||
PR 5333 |
Supports resistance thermometers |
|||||
PR 5334 |
Supports thermocouples |
|||||
PR 5335 |
4-20mА+HART |
Supports thermocouples and resistance thermometers |
||||
PR 5337 |
||||||
8 |
NSC and TT adjustment range |
K, 0…600°С |
Connected initial transmitter NSC, measurement range. |
FTT Exi-А44II -2-PR5334(K, 0…600С) – field measuring transmitter, explosion protection 0ExiaIICT6 X, case modification 44 with cable glands:«А» for unarmoured cable in RZ-CH-15 metal hose and two «I» for 3,2÷8,7 mm diameter unarmoured cable, two measuring transmitters PR5334, adjusted to NSC "K" and transmission range 0-600°С.